Damper Actuator,180 in-lb,Spring Return,24 to 240V (UP),On/Off,SW,NEMA 4HApplication | For On/Off, fail-safe control of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer?s specifications. Control is On/Off from an auxiliary contact or a manual switch. The actuator is mounted directly to a damper shaft up to 1.05? in diameter by means of its universal clamp. Maximum of two AF?s can be piggybacked for torque loads of up to 266 in-lbs. Minimum 3/4? diameter shaft and parallel wiring. Heater must remain powered at all times to ensure proper actuator operation at colder temperatures. |
---|
Servicing | maintenance free |
---|
Power Supply | 24...240 VAC +10% / -20%, 50/60 Hz, 24...125 VDC �10% |
---|
Power Consumption Running | 7 W |
---|
Power Consumption Holding | 3.5 W |
---|
Transformer Sizing | 7 VA @ 24 VAC (class 2 power source), 8.5 VA @ 120 VAC, 18 VA @ 240 VAC / heater 25 VA @ 120 VAC |
---|
Electrical Connection | (2) 3 ft [1 m], 18 GA appliance cables with 1/2? conduit connectors |
---|
Overload Protection | electronic throughout 0� to 95� rotation |
---|
Angle of Rotation | 95� (adjustable with mechanical end stop, 35� to 95�) |
---|
Direction of Rotation (Motor) | reversible with CW/CCW mounting |
---|
Manual Override | 5 mm hex crank (3/16? Allen), supplied |
---|
Running Time (Motor) | <75 sec |
---|
Ambient Temperature Range | -49�F to +122�F [-45�C to +50�C] |
---|
Storage Temperature Range | -40�F to +176�F [-40�C to +80�C] |
---|
Housing | NEMA 4, IP66, UL enclosure type 4 |
---|
Agency Listings | cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/EC |
---|
Noise Level (Motor) | �50 dB (A) |
---|
Direction of Rotation (Fail-Safe | reversible with CW/CCW mounting |
---|
Running Time (Fail-Safe) | 20 sec @ -4�F to +122�F [-20�C to +50�C], <60 sec @ -49�F [-45�C] |
---|
Noise Level (Fail-Safe) | <62 dB (A) |
---|
Housing Material | polycarbonate |
---|
Electrical protection | actuators are double insulated |
---|
Auxiliary Switch | 2 x SPDT, 3A resistive (0.5A inductive) @ 250 VAC, one set at +10�, one adjustable 10� to 90� |
---|
Shaft Diameter | 1/2? to 1.05? round, centers on 3/4? with insert, 1.05? without insert |
---|
Torque | 180 in-lbs [20 Nm] minimum |
---|
AF-P | Anti-rotation bracket AF/NF. |
---|
ZG-DC1 | Damper clip for damper blade, 3.5? width.
. |
---|
ZG-DC2 | Damper clip for damper blade, 6? width |
---|
TOOL-06 | 8 mm and 10 mm wrench. |
---|
PS-100 | Actuator power supply and control simulator. |
---|
KG10A | Ball joint for 3/8? diameter rod, zinc plated. |
---|
KH10 | Univ. crankarm, slot 21/64? w, for 9/16? to 1? dia. shafts. |
---|
SH10 | Push rod for KG10A ball joint (36? L, 3/8? diameter). |
---|
ZG-JSA-3 | 1.05? diameter jackshaft adaptor (12? L). |
---|
ZG-JSA-1 | 1? diameter jackshaft adaptor (11? L). |
---|
ZG-JSA-2 | 1-5/16? diameter jackshaft adaptor (12? L). |
---|
11097-00001 | Gasket for cable gland (for NEMA 4 models). |
---|
43442-00001 | Cable gland (for NEMA 4 models). |
---|
Operation | The AF..UP-S N4 series actuators provide true spring return operation for reliable fail-safe application and positive close off on air tight dampers. The spring return system provides constant torque to the damper with, and without, power applied to the actuator. The AF..UP-S N4 series provides 95� of rotation and is provided with a graduated position indicator showing 0� to 95�. The actuator may be stalled anywhere in its normal rotation without the need of mechanical end switches. The AF..UP-S N4 version are provided with two built-in auxiliary switches. These SPDT switches provide safety interfacing or signaling, for example, for fan start-up. The switching function at the fail-safe position is fixed at +10�, the other switch function is adjustable between +10� to +90�. The AF..UP-S N4 actuator is shipped at +5� (5� from full fail-safe) to provide automatic compression against damper gaskets for tight shut-off. |
---|
Typical Specification | On/Off spring return damper actuators shall be direct coupled type which require no crank arm and linkage and be capable of direct mounting to a jackshaft up to a 1.05? diameter. The actuators must be designed so that they may be used for either clockwise or counter clockwise fail-safe operation. Actuators shall be protected from overload at all angles of rotation. If required, two SPDT auxiliary switch shall be provided having the capability of one being adjustable. Actuators with auxiliary switches must be constructed to meet the requirements for Double Insulation so an electrical ground is not required to meet agency listings. Actuators shall be cULus listed and have a 5 year warranty, and be manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo. |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|