BALL VALVE 1" Cv 10Actuator Type | Spring return |
---|
Close Off Pressure | 200�psi |
---|
End Fitting | Internal thread |
---|
Control Type | Open-close only |
---|
Controllable Flow Range | 75� |
---|
Electrical Connection | cable |
---|
Flow Pattern | Mixing/Diverting |
---|
Application | This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. |
---|
Service | chilled, hot water, up to 60% glycol |
---|
Flow Characteristic | A-port equal percentage, B-port modified for constant common port flow |
---|
Controllable Flow Range | 75� |
---|
End Fitting | npt female ends |
---|
Body | forged brass, nickel plated |
---|
Stem Packing | EPDM (lubricated) |
---|
Seat O-ring | EPDM (lubricated) |
---|
Characterized Disc | TEFZEL? |
---|
Body Pressure Rating [psi] | 600 |
---|
Media Temperature Range (Water) | 0�F to 250�F [-18�C to 120�C] |
---|
Max Differential Pressure (Water) | 50 psi (345 kPa) |
---|
Close-Off Pressure | 200 psi |
---|
Leakage | 0% for A to AB, <2.0% for B to AB |
---|
Servicing | maintenance free |
---|
Power Supply | 24 VAC � 20%, 50/60 Hz, 24 VDC � 10% |
---|
Power Consumption Running | 5 W |
---|
Power Consumption Holding | 2.5 W |
---|
Transformer Sizing | 7 VA (class 2 power source) |
---|
Electrical Connection | 3ft [1m], 18 GA appliance cable with 1/2? conduit connector |
---|
Overload Protection | electronic throughout 0� to 95� rotation |
---|
Direction of Rotation (Motor) | reversible with built-in switch |
---|
Running Time (Motor) | <40 to 75 sec |
---|
Ambient Temperature Range | -22�F to 122�F [-30�C to 50�C] |
---|
Storage Temperature Range | -40�F to 176�F [-40�C to 80�C] |
---|
Agency Listings | cULus acc. To UL 873 and CAN/CSA C22.2 No. 24-93 |
---|
Noise Level (Motor) | <50 dB (A) |
---|
Direction of Rotation (Fail-Safe | reversible with CW/CCW mounting |
---|
Position Indication | visual indicator, 0� to 95� (0� is full spring return position) |
---|
Running Time (Fail-Safe) | <25 sec @ -4�F to 122�F [-20�C to 50�C], < 60 sec @ -22�F [-30�C] |
---|
Noise Level (Fail-Safe) | <62 dB (A) |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|