Belimo Aircontrols (USA), Inc. G680C+AFBUP-X1 3"flng 90Cv ON/OFF S/R 24-240V

Order QuantityUnit Price
Each$19,656.00
In Stock! Order Soon Ships in 24 hours
Availability: 1

3"flng 90Cv ON/OFF S/R 24-240V

ApplicationThis valve is typically used in large air handling units on heating or cooling coils. This valve is suitable for use in a hydronic system with variable flow. Bronze or stainless steel trim valves can be used for steam applications, depending on actuator and close-off combination
Servicechilled or hot water, up to 60% glycol, steam
Flow Characteristicequal percentage
Controllable Flow Rangestem up - open A to AB
Size [mm]3? [80]
End Fitting125 lb flanged
Bodycast iron - ASTM A126 Class B (ASMEB16.1)
Stemstainless steel
Stem PackingNLP EPDM (no lip packing)
Seat316 stainless steel
Body Pressure Rating [psi]ANSI 125
Media Temperature Range (Water)32�F to 338�F [0�C to 138�C]
Max Differential Pressure (Water)25 psi (172 kPa)
Cv90
Weight75 lb [34 kg]
LeakageANSI Class III
ServicingRepack/Rebuild kits available
Power Supply24...240 VAC +10% / -20%, 50/60 Hz, 24...125 VDC �10%
Power Consumption Running7 W
Power Consumption Holding3.5 W
Transformer Sizing7 VA @ 24 VAC (class 2 power source), 8.5VA @ 120 VAC, 18 VA @ 240 VAC
Electrical Connection3 ft [1 m], 18 GA appliance cable with 1/2?conduit connector
Overload Protectionelectronic throughout 0� to 95� rotation
Angle of Rotation95� (adjustable with mechanical end stop,35� to 95�)
Direction of Rotation (Motor)reversible with built-in switch
Manual Override5 mm hex crank (3/16? Allen), supplied
Running Time (Motor)<75 sec
Ambient Temperature Range-22�F to +122�F [-30�C to +50�C]
Storage Temperature Range-40�F to +176�F [-40�C to +80�C]
HousingNEMA 2, IP54, UL enclosure type 2
Agency ListingscULus acc. to UL60730-1A/-2-14, CAN/CSAE60730-1:02, CE acc. to 2004/108/EC and 2006/95/EC
Noise Level (Motor)<50 dB (A)
Quality StandardISO 9001
Operating Range Yon/off
Direction of Rotation (Fail-Safereversible with CW/CCW mounting
Position Indicationvisual indicator, 0� to 95� (0� is full spring return position)
Running Time (Fail-Safe)<20 sec
Noise Level (Fail-Safe)<62 dB (A)
Housing Materialzinc coated metal and plastic casing
Max Inlet Pressure (Steam)35 psi (241 kPa)
Media Temperature Range (Steam)32�F to 280�F [0�C to 138�C]
Maximum Differential Pressure (Steam)15 psi (103 kPa)
Humiditymax. 95% RH non-condensing
Number of Bolt Holes4
Plugbrass
ANSI ClassANSI 125 (up to 175 psi below 150�F)
Rangeability91:1
Max Inlet Pressure (Water)150 psi (1034 kPa) @ 250�F
PipingThe valves should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. The preferred mounting position of the valve is with the valve stem vertical above the valve body, for maximum life. However, the assemblies can be mounted with valve stem vertical above the valve or up to 45 degrees in relation to the horizontal pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction.

Product Family

Model NumberDecriptionManufacturerPriceAvail. Qty 
G680CAFBUPX1 3"flng 90Cv ON/OFF S/R 24-240V Belimo Aircontrols (USA), Inc. $19,656.00 1    Add To Cart

Coming Soon

All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.

UPS Hoilday Delivery Schedule

For more infomation about Returns visit Returns

For more informatrion about Warranty visit Warranty page.

You can also find answers to some common questions on our FAQ page

Reviews

Not reviewed yet, be the first to write one!

Add Review