VALVE: 2-way CCV, Flanged SS Trim, 2-1/2", Cv 70 , ACTUATOR: Actuator 20 Nm, 150 s adjustable, AC / DC 24 V, modulating, MFT IP 54, Manual override with push-button Control DC 2...10 V, 0...32 V adjustable Operating range DC 2...10 V, 0...32 V adjustable Position feedback DC 2...10 V, 0...10 V,adjustable DireApplication | This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow |
---|
Service | chilled, hot water, up to 60% glycol |
---|
Flow Characteristic | equal percentage |
---|
Controllable Flow Range | 75° |
---|
End Fitting | pattern to mate with ANSI 125 flange |
---|
Stem Packing | EPDM (lubricated) |
---|
Seat O-ring | EPDM (lubricated) |
---|
Characterized Disc | stainless steel |
---|
Body Pressure Rating [psi] | ANSI 125, standard class B |
---|
Media Temperature Range (Water) | 0°F to 250°F [-18°C to 120°C] |
---|
Max Differential Pressure (Water) | 50 psi (345 kPa) |
---|
Close-Off Pressure | 100 psi |
---|
Servicing | maintenance free |
---|
Power Supply | 24 VAC ± 20%, 50/60 Hz, 24 VDC ± 10% |
---|
Power Consumption Running | 3.5 |
---|
Power Consumption Holding | 1.3 W |
---|
Transformer Sizing | 6 VA (class 2 power source) |
---|
Electrical Connection | 18 GA plenum rated cable with 1/2” conduit
connector protected NEMA 2 (IP54) 3ft [1m]
10ft [3m] and 16ft [5m] |
---|
Overload Protection | electronic thoughout 0° to 90° rotation |
---|
Input Impedance | 100 k ? for 2 to 10 VDC (0.1 mA), 500 ? for 4
to 20 mA, 1500 ? for PWM, floating point and
On/Off |
---|
Direction of Rotation (Motor) | reversible with built-in switch |
---|
Manual Override | external push button |
---|
Running Time (Motor) | 150 sec (default), variable (90 to 150 sec) |
---|
Ambient Temperature Range | -22°F to 122°F [-30°C to 50°C] |
---|
Storage Temperature Range | -40°F to 176°F [-40°C to 80°C] |
---|
Housing | NEMA 2, IP42, UL enclosure type 2 |
---|
Agency Listings | cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC |
---|
Noise Level (Motor) | <45 dB (A) |
---|
Operating Range Y | 2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500 ?,
1/4 W resistor), variable (VDC, floating point,
on/off) |
---|
Position Indication | integrated into handle |
---|
Feedback Output U | 2 to 10 VDC, 0.5 mA max, VDC variable |
---|
ZS-CCV. | New Characterized Control Valve Weather Shield |
---|
S1A, S2A | Auxiliary Switches |
---|
P...A | Feedback Potentiometer |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|