Damp.Rotary, 360in-lb, On/Off/Float, 24VActuator Type | Electronic fail-safe |
---|
Control Type | Floating/3-point |
---|
Electrical Connection | cable |
---|
Direction of Rotation (Fail-Safe) | reversible with switch |
---|
Direction of Rotation (Motor) | reversible with built-in switch |
---|
Power Consumption (Holding) | 3�W |
---|
Power Consumption (Running) | 11 W |
---|
Degree of Protection | NEMA�2, UL�Enclosure�Type�2 |
---|
Shaft Diameter | 1/2" to 1.05" round, centers on 3/4" with insert, 1.05" without insert |
---|
Manual Override | external push button |
---|
Application | For on/off and fl oating point, fail-safe control of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer?s specifi cations. The actuator is mounted directly to a damper shaft up to 1.05? in diameter by means of its universal clamp. The actuator is mounted directly to a damper shaft up to 1.05? in diameter by a universal clamp. A crank arm and several mounting brackets are available for applications where actuator cannot be direct coupled to the damper shaft. Control is fl oating point from a triac or relay, or On/Off from an auxiliary contact from a fan motor contactor, controller or manual switch. |
---|
Servicing | maintenance free |
---|
Power Supply | 24VAC �20% 50/60Hz |
---|
Electrical Connection | 18 GA plenum rated cable �" conduit connector protected NEMA 2 (IP54) 3 ft [1m] 10 ft [3m] 16 ft [5m] |
---|
Overload Protection | electronic throughout 0 to 95 rotation |
---|
Angle of Rotation | max. 95�, adjustable with mechanical stop electronically variable |
---|
Manual Override | external push button |
---|
Housing | NEMA2, IP54, UL enclosure type 2 |
---|
Position Indication | refl ective visual indicator (snap-on |
---|
Feedback Output U | 2 to 10VDC, 0.5mA max, VDC variable |
---|
Ambient temperature | -22�F to +122�F [-30�C to +50�C] |
---|
Humidity | 5 to 95% RH non-condensing (EN 60730-1) |
---|
Direction of Rotation | reversible with switch |
---|
Bridge Time | 2 second delay before fail-safe activates |
---|
Storage temperature | 40�F to +176�F [-40�C to +80�C] |
---|
Power consumption | 12W (3W) |
---|
Fail-Safe Position | adjustable with dial, 0 to 1 in 10� increments |
---|
Operation range Y | on/off, fl oating point |
---|
Running time normal operation fail-saf | 150 seconds (default), variable 90 to 150 seconds 35 second |
---|
Agency list | cULus acc. to UL 60730-1A/-2-14 CAN/CSA E60730-1:02 CE acc. to 2004/108/EC and 2006/95/EC |
---|
n 12W (3W) Transformer sizing | 21VA (class 2 power source) |
---|
nitial charge | 5 to 20 seconds |
---|
S1A, S2A | Auxiliary Switch(es) |
---|
P...A | Feedback Potentiometers |
---|
ZS-100 | Weather Shield - Steel |
---|
ZS-150 | Weather Shield - Polycarbonate |
---|
ZS-260 | Explosion Proof Housing |
---|
ZG-JSA (-1, 2,3) | Jackshaft Adaptors for Hollow Jackshafts |
---|
ZS-300 (-1) (-5) | NEMA 4X Housing |
---|
PS-100 | Actuator Power Supply Simulator |
---|
P370 | Shaft Mount Auxiliary Switch |
---|
K-GM20 | ?" [20mm] Shaft Clamp |
---|
ZG-102 | Multiple Actuator Mounting Bracket |
---|
ZG-GMA | Crank arm Adaptor Kit |
---|
Operation | The GK..24-3 actuator provides 95� of rotation and a visual indicator shows the position of the actuator. When reaching the damper or actuator end position, the actuator automatically stops. The gear can be manually disengaged by pressing the button located on the actuator cover. The GK..24-3 actuators use a brushless DC motor, which is controlled by an Application Specifi c Integrated Circuit (ASIC). The ASIC monitors and controls the actuators rotation and provides a digital rotation sensing (DRS) function to prevent damage to the actuator in a stall condition. Power consumption is reduced in a holding mode. The actuator is electronically protected against overload. The anti-rotation strap supplied with the actuator will prevent lateral movement. Add-on auxiliary switches or feedback potentiometers are easily fastened directly onto the actuator body for signaling and switching functions. |
---|
Typical Specification | On/off, fl oating point control damper actuators shall be electronic directcoupled type, which require no crank arm and linkage and be capable of direct mounting to shaft up to 1.05" diameter. Actuators shall have brushless DC motor technology and be protected from overload at all angles of rotation. Actuators shall have reversing switch and manual override on the cover. Run time shall be constant and independent of torque. Actuators shall be cULus listed, have a 5-year warranty, and be manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo. |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|