• Universal model (T775U) can control pressure, humidity, or any variable analog input. • Special boiler model (T775P) for boiler control. • Special Staged Sequencing Model (T775L) for sequence staging of relays with one or two setpoints. • Special Expansion Model (T775S) for staging up to 12 relays with two setpoints (each T775S provides 4 relays). • Save time on installations with the easy-to-use graphical Interface, large display, and the intuitive programming. • Use the time clock scheduler or digital input to control the setback and disable output options to help save energy. • Provide very fast or very fast response times on modulating outputs by adjusting the integral and derivative times (PI or PID). • Configure models with reset in a few easy steps. • Eliminate the need for a separate time delay device and protect equipment with the minimum off time option. • Use the T775L and T775P to stage up to 12 relays (with optional T775S) from two independent heat or cool setpoints. • Support for digital output alarm on the T775P configurable based on minimum, maximum, or differential temperature.T775L2007/U Electronic Temperature Controller/Sequencer/Reset option,2 Temp Input, 1 sensor includedAnalog Output | Electronic Series 90; 4-20 mA; 0-10 Vdc; 2-10 Vdc |
---|
Overview | The T775 electronic remote temperature controllers are the next generation of commercial and agricultural controls capable of remote sensing of temperature, humidity, pressure, etc., and providing switched and/or proportional outputs to various types of l |
---|
Approvals, Others | IP65: Approved |
---|
Relay Contact Ratings (24 Vac) | 10.0A resistive |
---|
Operating Temperature Range (F) | Ambient-- -40 F to 125 F @ 50 Hz; -40 F to 140 F @ 60 Hz |
---|
Relay Contact Ratings (120 Vac) | 1/2 hp; 9.8 AFL, 58.8 ALR, 125 VA Pilot Duty |
---|
Operating Temperature Range (C) | Ambient-- -40 C to 52 C @ 50 Hz; -40 C to 60 C @ 60 Hz |
---|
Type | Stage Sequencer with Reset Option-NEMA 1 |
---|
Relay Contact Ratings (240 Vac) | 1/2 hp; 4.9 AFL, 29.4 ALR, 125 VA Pilot Duty |
---|
Sensors Included | 50021579-001 (1) |
---|
Application | Staging controller for applications where electronic accuracy and remote sensing of temperature is required. |
---|
Maximum distance to sensor (ft) | Up to 1,000 ft |
---|
Maximum distance to sensor (m) | up to 304 m |
---|
Bulb Size (in.) | 1/4 in. diameter x 2 in. long |
---|
Sensor Element | 1097 ohms PTC at 77 F (25 C) |
---|
Bulb Size (mm) | 6.35 mm diameter x 50.8 mm |
---|
Setpoint Temperature Range (F) | -40 F to 248 F |
---|
Setpoint Temperature Range (C) | -40 C to 120 C |
---|
Throttling Range (F) | 1 F to 150 F |
---|
Throttling Range (C) | 0.5 C to 66 C |
---|
Differential Temperature (F) | 1 F to 150 F |
---|
Voltage | 24 Vac or 120/240 Vac |
---|
Differential Temperature (C) | 0.5 C to 66 C |
---|
Expandable | Add 1 or 2 T775Ss (4 relays ea) |
---|
Operating Ambient Temperature Range (F) | -40 F to 140 F @ 60 Hz |
---|
Operating Ambient Temperature Range (C) | -40 C to 52 C @ 50 Hz |
---|
Dimensions (in.) | 8 5/32 in. high x 4 13/32 in. wide x 2 15/16 in. deep |
---|
Dimensions (mm) | 207.1 mm high x 112.1 mm wide x 74 mm deep |
---|
Approvals, Canadian Underwriters Laboratories | Approved |
---|
Approvals, Underwriters Laboratories Inc | Approved |
---|
Approvals, C-Tick | Approved |
---|
Analog Output Type | 4-20 mA |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|