• Used for combination or dual-fuel applications.
• Detects pilot and main flame.
• Mounts quickly and easily on a standard 3/4 in. sighting pipe.
• Works where flame rod or rectifying photocell mounts are difficult to apply.
• The C7915 includes 50019469-001 Bushing with magnifying lens.
• The C7915 uses photoconductive lead sulfide cells 32007255-001.Solid State Infrared Scanner 48in LeadsOverview | The C7915 Flame Detectors include a lead sulfide photocell that is sensitive to the infrared radiation emitted by the combustion of fuels such as natural gas, oil, and coal. |
---|
Ambient Temperature Range (F) | -20F to 125F operating range |
---|
Ambient Temperature Range (C) | -18C to 52 operating range |
---|
Type | Infrared (Lead Sulfide) |
---|
Application | Used for combination or dual-fuel applications |
---|
Electrical Connections | Two no.18 AWG wires |
---|
Includes | With magnifying lens, 32007255-001 Cell, Orifice, heat block, and reducer bushing |
---|
Dimensions (in.) | 1 1/4 in. diameter x 2 1/4 in. long |
---|
Dimensions (mm) | 32 mm diameter x 58 mm long |
---|
Approvals, Underwriters Laboratories Inc | Listed: File No. MP268, Guide No. MCCZ |
---|
Approvals, Canadian Standards Association | Certified: Master Report LR95329-1 |
---|
Approvals, Swiss RE (formerly IRI) | Acceptable |
---|
Approvals, Factory Mutual | Approved: Report No. 24181.03 |
---|
Comments | Infrared (Lead Sulfide) Flame Detector |
---|
Used With | Flame Amplifiers: R7852 |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|