Description:
- Electronic-Pneumatic Transducers are utilized in electronic-pneumatic control systems to convert a proportional electric output signal from a controller into a direct-acting, proportional pneumatic signal.
Features:
- Available in screw mounting or snap rail (models with cover).
- Factory calibrated for convenience.
- Equipped with dual barb fittings for easy connections.
- Offers high accuracy for precise control.
Specifications:
- Application: Electric to pneumatic Transducer
- Maximum Safe Operating Pressure: 30 psi
- Output Pressure Range: 3 to 15 psi
- Connections: Dual barb-fittings compatible with 1/4 in. or 5/32 in. O.D. plastic tubing
- Airflow Usage: 0.025 scfm (117mL/s)
- Max. Operating Temperature: 131 F
- Input Signal: 2 to 10 Vdc
- Normal High End Pressure: 16 psi with 18 psi main pressure at 12 Vdc or 16 psi at 11 Vdc (min.)
- Normal Low End Pressure: 0.5 psi at 0 Vdc
- Pressure Range: 0 to 18 psi
- Voltage: Powered by Control signal
- Humidity Range: 5 to 95% RH
- Comments: Does not include cover or internal power supply for panel mounting (2 wire)
- 0.45 SCFM Electronic-Pneumatic Transducer, 3-wire
Application | Electric to pneumatic Transducer |
---|
Input Signal | 2 to 10 Vdc at 0.1 mA max |
---|
Nominal High End (psi) | 16 psi with 18 psi main pressure at 12 Vdc or 16 psi at 11 Vdc ( min. ) |
---|
Capacity | 0.45 scfm (211 mL/s) |
---|
Overview | Electronic-Pneumatic Transducers are used in electronic-pneumatic control systems to convert a proportional electric output signal from a controller into a direct-acting, proportional pneumatic signal. |
---|
Nominal High End (kPa) | 116 kPa with 125 kPa main pressure at 12 Vdc or 110 kPa at 11 Vdc ( min. ) |
---|
Nominal Low End (psi) | 0.5 psi at 0 Vdc |
---|
Electrical Connections | 30 in. (762 mm) lead wire |
---|
Connections | Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic tubing |
---|
Nominal Low End (kPa) | 3.5 kPa at 0 Vdc |
---|
Output Pressure Range (psi) | 3 to 15 psi |
---|
Pressure Range (psi) | 0 to 18 psi |
---|
Output Pressure Range (kPa) | 21 to 103 kPa |
---|
Pressure Range (kPa) | 0 to 125 kPa |
---|
Voltage | 24 Vac external transformer |
---|
Maximum Operating Temperature (F) | 131 F |
---|
Maximum Operating Temperature (C) | 55 C |
---|
Maximum Safe Operating Pressure (psi) | 30 psi |
---|
Airflow Usage | 0.025 scfm (117mL/s) |
---|
Maximum Safe Operating Pressure (kPa) | 205 kPa |
---|
Operating Humidity Range (% RH) | 5 to 95% RH |
---|
Dimensions (in.) | 2 7/16 in. wide x 3 5/8 in. high x 2 in. deep |
---|
Dimensions (mm) | 62 mm wide x 92 mm high x 52 mm deep |
---|
Includes | With cover, external transformer required, 24 Vac, 50/60 Hz, (3 wire) |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|