• Transformer powers low voltage control systems and provides overload protection.
• Low voltage terminal board provides convenient connections for thermostat and heating/cooling equipment wiring.
• Mounts on standard 4 x 4 in. junction box.
• Relay is easily replaced without disturbing wiring.Control Center, DPDTApplication | For "Total Comfort" applications with electronic air cleaner, humidifier and blower motor. |
---|
Overview | Provides low voltage control of line voltage fan motors and auxiliary circuits in heating, cooling, or air conditioning systems.
This product is obsolete. It can be purchased while supply lasts, or you can look for a replacement in the cross-reference. |
---|
Electrical Ratings (W) | 11 W maximum |
---|
Power Supply (Secondary) | 26.5 V |
---|
Electrical Ratings | 11 W maximum |
---|
Electrical Ratings (120 Vac, Full Load) | 12A |
---|
Electrical Ratings (120 Vac, Locked Rotor) | 72A |
---|
Electrical Ratings (240 Vac, Full Load) | 6A |
---|
Electrical Ratings (240 Vac, Locked Rotor) | 35A |
---|
Dimensions (in.) | 4 3/16 in. high, 4 1/2 in. wide, 2 13/16 in. deep. |
---|
Dimensions (mm) | 106 mm high, 114 mm wide, 71 mm deep |
---|
Approvals, Underwriters Laboratories Inc | UL Component Recognized; File No. E4436, Vol.15, Sec.1, Guide No.XAPX2 |
---|
Approvals, Canadian Standards Association | Certified: File No. LR95329-17 |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.