BACnet® Details:
•
MS/TP Address & Baud Rate must be set prior
to power up via DIP switches.
•
Device ID will default to 277XXX where XXX is
the MS/TP Address.
Examples:
•
Device ID can be changed via network
command. Once changed, it will no longer
default to 277XXX. (MS/TP Address & Device
ID must be unique.)
•
Devices Instance changed via Object
Identifier Property of Device Object.
•
Status of UPS connection, Battery run time,
line power ,UPS load (VA and %), and battery
capacity can be read from BACnet network.