Energy Valve, 0.5", 2-Way, 5.5GPM w/Non Spring,Actuator Type | Non fail-safe |
---|
Close Off Pressure | 200�psi |
---|
End Fitting | Internal thread |
---|
Electrical Connection | cable |
---|
Communication | BACnet IP, BACnet MS/TP, listed by BTL, Modbus RTU, Modbus IP, web server, Belimo MP-Bus |
---|
Service | chilled or hot water, up to 60% glycol max
(open loop/steam not allowed) |
---|
Flow Characteristic | equal percentage or linear |
---|
End Fitting | NPT female ends |
---|
Body | forged brass, nickel plated |
---|
Stem Packing | EPDM (lubricated) |
---|
Characterized Disc | TEFZEL? |
---|
Body Pressure Rating [psi] | 360 |
---|
Media Temperature Range (Water) | 14�F to 250�F [-10�C to 120�C |
---|
Close-Off Pressure | 200 psi |
---|
Servicing | maintenance free |
---|
Power Supply | 24 VAC � 20%, 50/60 Hz, 24 VDC � 10% |
---|
Power Consumption Running | 4 W |
---|
Transformer Sizing | 7 VA (class 2 power source) |
---|
Electrical Connection | 18 GA plenum rated cable and RJ45 socket
(ethernet) |
---|
Overload Protection | electronic thoughout 0� to 90� rotation |
---|
Input Impedance | 100 k? (0.1 mA), 500 ? |
---|
Angle of Rotation | 90�, adjustable with mechanical stop |
---|
Direction of Rotation (Motor) | reversible with web view |
---|
Manual Override | external push button |
---|
Running Time (Motor) | 90 sec |
---|
Ambient Temperature Range | -22�F to 122�F [-30�C to 50�C] |
---|
Storage Temperature Range | -40�F to 176�F [-40�C to 80�C] |
---|
Housing | NEMA 1, IP54, UL Enclosure Type 1 |
---|
Agency Listings | cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC and
2006/95/EC |
---|
Noise Level (Motor) | max. 45 dB (A) |
---|
Operating Range Y | 2 to 10 VDC (default) VDC variable |
---|
Position Indication | integrated into handle |
---|
Feedback Output U | 2 to 10 VDC (default) VDC variable |
---|
Ambient Humidity | <95% RH non-condensing |
---|
Flow Measurement Tolerance | �2%* |
---|
Flow Measurement Repeatability | +/- 0.5% |
---|
Sensor Technology | ultrasonic with glycol and temperature
compensation |
---|
Sensor Housing | forged brass, nickel plated |
---|
Differential Pressure Range | 5 to 50 psid or 1 to 50 psid see flow
reductions chart in tech doc |
---|
Inlet Length to Meet Specified
Measurement Accuracy | 5X nominal pipe size (NPS) |
---|
Flow Control Tolerance | �5% |
---|
emperature Sensors | PT1000 insertion sensors w/NPT body |
---|
Temperature Measurement
Tolerance | According to PT1000 DIN EN60751 ClassB |
---|
Resolution of Temperature Sensor | 0.18�F (0.1�C) |
---|
Rated Impulse Voltage | actuator/sensor: 0.8 kV (in accordance with EN60730-1) kV |
---|
Power Supply for the Flow Sensor | sensor is powered by the actuator |
---|
Remote Temperature Sensor Length | Standard: 2 ft. 7.5 in. [0.8m], 9.8 ft. [3m] |
---|
Degree of Protection IEC/EN | IP54 |
---|
Degree of Protection NEMA/ UL | NEMA 1, UL Enclosure Type 1 |
---|
Glycol Measurement Accuracy | +/-5% |
---|
Communication | BACnet IP, BACnet MS/TP, listed by BTL,
Modbus RTU, Modbus IP, web server, Belimo
MP-Bus |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|