CO2 Temp/HumidSnsr, TAC VistaDimensions Depth | See Diagram |
---|
Dimensions Height | See Diagram |
---|
Dimensions Width | See Diagram |
---|
Standards EMC | EN 61000-6-3: 2007 Class B |
---|
BAS Compatibility | TAC Vista |
---|
Dimensions Probe Length | See Diagram |
---|
Accuracy | Plus or minus 1.5% of measurement range; Plus or minus 2% of measured value |
---|
Humidity Measurement Range | 0 to 100% RH |
---|
Measurement Type | Carbon Dioxide (CO2) |
---|
Sensor Output | 1.8K Ohm at 25 C (77 F) |
---|
Dimensions Diameter | See Diagram |
---|
Material Enclosure | ABS Plastic |
---|
Operating Humidity Range | 0 to 95% RH, non-condensing |
---|
Operating Temperature Range | 0 to 50 C (32 to 122 F) |
---|
Supplier | Schneider Electric |
---|
Repeatability | Plus or minus 20 ppm Plus or minus 1% of measured value |
---|
Response Time | Less than 60 seconds for 90% step change |
---|
Stability | Plus or minus 1% at 20 C (68 F) annually, for two years |
---|
Inputs | 24 VAC, 20 to 36 VDC Class 2 |
---|
Measurement Range | 0 to 2000 ppm |
---|
Sensor Type | Non-dispersive infrared (NDIR), diffusion sampling |
---|
Current Draw | 20 to 36 VDC 40mA avg., 105mA max.; 24 VAC 50mA avg., 150mA max. |
---|
Temperature Coefficient | Plus or minus 0.1% RH/ C above or below 25 C (typical) |
---|