VALVE: BALL VALVE 3/4" Cv 4.7 , ACTUATOR: Valve Act, 24V AC/DC, 45 in-lb (5Nm) 2 to 10 VDC Input 1m Plenum Cable Single Unit, Conduit Fitting CCV LinkageApplication | This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow. |
---|
Service | chilled, hot water, up to 60% glycol |
---|
Flow Characteristic | A-port Equal percentage; B-port modified
linear for constant flow |
---|
Controllable Flow Range | 75° |
---|
End Fitting | npt female ends |
---|
Body | forged brass, nickel plated |
---|
Stem Packing | EPDM (lubricated) |
---|
Seat O-ring | EPDM (lubricated) |
---|
Characterized Disc | TEFZEL® |
---|
Body Pressure Rating [psi] | 600 |
---|
Media Temperature Range (Water) | 0°F to 250°F [-18°C to 120°C] |
---|
Max Differential Pressure (Water) | 50 psi (345 kPa) |
---|
Close-Off Pressure | 200 psi |
---|
Leakage | 0% for A to AB, <2.0% for B to AB |
---|
Servicing | maintenance free |
---|
Power Supply | 24 VAC ± 20%, 50/60 Hz, 24 VDC ± 10% |
---|
Power Consumption Running | 1.5 W |
---|
Power Consumption Holding | 0.4 W |
---|
Transformer Sizing | 3 VA (class 2 power source) |
---|
Electrical Connection | 3ft [1m], 18 GA plenum cable with 1/2” conduit
connector |
---|
Overload Protection | electronic thoughout 0° to 90° rotation |
---|
Input Impedance | 100 k ? for 2 to 10 VDC (0.1 mA), 500 ? for 4
to 20 mA |
---|
Direction of Rotation (Motor) | reversible with built-in switch |
---|
Manual Override | external push button |
---|
Running Time (Motor) | 90 sec |
---|
Ambient Temperature Range | -22°F to 122°F [-30°C to 50°C] |
---|
Storage Temperature Range | -40°F to 176°F [-40°C to 80°C] |
---|
Housing | NEMA 2, IP42, UL enclosure type 2 |
---|
Agency Listings | cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC |
---|
Noise Level (Motor) | <35 dB (A) |
---|
Operating Range Y | 2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500 ?,
1/4 W resistor) |
---|
Position Indication | integrated into handle |
---|
Feedback Output U | 2 to 10 VDC |
---|
ZS-CCV. | New Characterized Control Valve Weather Shield |
---|
S1A, S2A | Auxiliary Switches |
---|
P...A | Feedback Potentiometer |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!