• The control communicates directly with the ST9160 Electronic Fan Timer (EFT) in typical forced warm air furnace applications.
• It will also interface with the 208907 Terminal Board, providing compatibility with power-stealing thermostats. Or, it directly interfaces with the appropriate power supplies and a system thermostat for additional appliance applications.
• When controlled directly by a thermostat, the control does not provide a postpurge function, as power to the control is removed when the thermostat call for heat ends.
• This system is suitable for a wide range of fan-assisted combustion, gas-fired appliances including furnaces, rooftop furnaces, boilers, unit heaters, infrared heaters, water heaters and commercial cooking appliances.DIR HSI SMRT VLV .5X.5 NAT GASControl Voltage (Thermostat or other call for heat) | 24 Vac, 60 Hz. |
---|
Overview | The SV9510 SmartValve® System Controls combine gas flow control and electronic direct main burner ignition sequencing functions into a single unit. The ignition source is 120V hot surface igniter lighting the main burner flame. Provides all gas ignition s |
---|
Pressure Tapping | 1/8 in. - NPT |
---|
Includes | LP Conversion Kit |
---|
Tradeline Value | Super Tradeline |
---|
Ignition System Type | Direct Hot Surface Ignition |
---|
Mounting | 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically. |
---|
Dimensions (in.) | 3.2 in. wide x 4.9 in. high x 4.1 in.long |
---|
Ignition Sequence | 17/27 sec |
---|
Dimensions (mm) | 81 mm wide x124 mm high x 104 mm long. |
---|
Ignition Trials To Lockout | 4 trials |
---|
Body Pattern | Straight-through |
---|
Opening Characteristics (standard, step) | Standard Opening |
---|
Ignition Trial Time (sec) | 7 sec |
---|
Flame Failure Response Time (sec) | 2 sec @ 5 µA |
---|
Ambient Temperature Range (F) | -40 F to +175 F |
---|
Ambient Temperature Range (C) | -40 C to +79 C |
---|
Pressure Regulator Setting (psi) | 3.5 in. wc |
---|
Pressure Regulator Setting (kPa) | 0.87 kPa |
---|
Pressure Ratings (psi) | 1/2 psi |
---|
Pressure Ratings (kPa) | 3.5 kPa |
---|
Inlet/Outlet Size (in.) | 1/2 in. NPT x 1/2 in. NPT |
---|
Maximum Capacity (ft³/hr) | 200 ft³/hr |
---|
Maximum Capacity (m³/hr) | 5.7 m³/hr |
---|
Minimum Capacity (ft³/hr) | 20 ft³/hr |
---|
Minimum Capacity (m³/hr) | 0.6 m³/hr |
---|
Maximum Capacity at 1 in. P.D. (ft³/hr) | 150 ft³/hr |
---|
Maximum Capacity at 1 in. P.D. (m³/hr) | 4.2 m³/hr |
---|
Typical Ignition Hardware | Norton 271 |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|