• Y8610U kits are for use with natural or LP gas: provides 100 percent pilot gas shutoff if pilot fails to light; after 6-minute delay, trial for ignition is repeated.
• Ignition trail/delay sequence is repeated until the appliance lights or call for heat is removed.S8610F VR8204A 1/2 BY 1/2 3.5 IN. WOverview | Complete kits converting conventional standing pilot system to intermittent pilot system. For use with 24 Vac gas-fired atmospheric furnaces, boiler and heating appliances. |
---|
Ignition System Type | Intermittent Pilot |
---|
Ignition Sequence | Continuous retry, after trial for ignition, pilot gas shuts off for 5 minutes, then another trial for pilot ignition takes place |
---|
Typical Gas Control | VR8204, VR8304 |
---|
Flame Sense | Single Rod or Two Rods |
---|
Ignition Source | Internal high voltage spark generator |
---|
Ignition Trials To Lockout | continuous retry |
---|
Lockout Timing | 15 or 90 seconds |
---|
Ignition Trial Time (sec) | 15 or 90 seconds |
---|
Maximum Valve Load @ 24 Vac (Amps) | 1A Pilot, 2A Main @ 24Vac |
---|
Typical Ignition Hardware | Q345, Q3451 |
---|
Dimensions (in.) | 3 15/16 in. high x 5 7/16 in. wide x 2 5/8 in. deep |
---|
Dimensions (mm) | 100 mm high x 138 mm wide x 67 mm deep |
---|
Maximum Ambient Temperature (F) | -40 F to +165 F |
---|
Maximum Ambient Temperature (C) | -40 C to +74 C |
---|
Includes | VR8204A2142 valve (1/2 x 1/2; 3.5" WC setting; 150 kBtu/hr at 1" p.d.) |
---|
Flame Failure Response Time (sec) | 2.0 sec |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|