Damper Actuator SprApplication | The type FSLF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper and will meet requirements of UBC for 15 second opening and closing. Square footage of damper operated will depend on make and model and the temperature required. IMPORTANT 24VDC NOTE: The FSLF24 & -S models will not operate below 24VDC. A filtered and regulated power supply must be used. |
---|
Servicing | maintenance free |
---|
Power Supply | 24 VAC � 10%, 24-36 VDC |
---|
Power Consumption Running | 50/60 Hz, 15 VA |
---|
Power Consumption Holding | 3.5 VA, End Stop 25 VA, 1 A slow blow fuse * |
---|
Transformer Sizing | 24 VA (class 2 power source) |
---|
Electrical Connection | 3 ft [1 m], 18 GA, 2 color coded leads |
---|
Overload Protection | electronic throughout 0� to 95� rotation |
---|
Direction of Rotation (Motor) | can be selected by CCW/CW mounting |
---|
Running Time (Motor) | <15 sec at rated voltage and torque 32�F to 122�F [0�C to 50�C] |
---|
Ambient Temperature Range | 32�F to 122�F [0�C to 50�C] |
---|
Storage Temperature Range | -40�F to 176�F [-40�C to 80�C] |
---|
Direction of Rotation (Fail-Safe | can be selected by CCW/CW mounting |
---|
Position Indication | visual indicator, 0� to 95� (0� is full spring return position) |
---|
Running Time (Fail-Safe) | <15 sec |
---|
Noise Level (Fail-Safe) | 45 dB (A) motor, 62 dB (A) spring, inaudible
holding |
---|
Housing Material | zinc coated steel |
---|
Electrical protection | actuators are double insulated |
---|
Humidity | 5 to 95% RH non-condensing |
---|
Auxiliary Switch | 2 x SPST, 0.5 A inductive @120/250 V, 1 mA
@ 5 VDC, 3 A resistive @ 120/250 V, 10� and
85�, double insulated |
---|
Shaft Diameter | 3/8? to 1/2? round, centers on 1/2? |
---|
Torque | 30 in-lbs [3.5 Nm] minimum from 32�F to 350�F [0�C to 177�C] |
---|
BAE165 US | 165� F electric thermal sensor, SPST, normally closed. |
---|
S2A-F US | Auxiliary switch, 2x SPDT, 3A (0.5A inductive) @250 VAC max. |
---|
Operation | Mounting of the actuator to the damper axle shaft or jackshaft is via a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an anti-rotation strap or by a stud provided by the damper manufacturer. The actuator is mounted in its fail safe position with the damper blade(s) closed. Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position |
---|
Typical Specification | All smoke and combination fire and smoke dampers shall be provided with Belimo FSTF, FSLF, FSNF, or FSAF actuators. All substitutions must be approved before submission of bid. Damper and actuator shall have UL 555S Listing for 250�F (350�F). Actuator shall have been tested to UL 2043 per requirements of IMC 602.2 and NEC 300.22 (c). Where position indication is required -S models with auxiliary switches or damper blade switches will be provided per code requirements. |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|