• Flame failure response time of 0.8 or 3.0 seconds. • Flame signal strength ranges from 0.0 to 5.0 Vdc. • Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation. • Flame signal test jacks to measure amplifier flame signal voltage. • Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure. • Compatible with existing Honeywell flame detectors (order separately).Amplifier Dynamic Shutter CheckSelf Checking | Dynamic Self-Check |
---|
Flame Failure Response Time (sec) | 2.0 sec or 3.0 sec |
---|
Overview | Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules. |
---|
Use With Primary Safety Control | 7800 SERIES Relay Modules |
---|
Use With Flame Sensor | Gas, oil, coal: optical (UV only) C7961E,F |
---|
Approvals, Underwriters Laboratories Inc | Listed: File No. MP268, Guide No. MCCZ |
---|
Approvals, Canadian Standards Association | Certified: File No. LR95329-3 |
---|
Approvals, Swiss RE (formerly IRI) | Acceptable |
---|
Approvals, Factory Mutual | Approved: Report No. 1V9A0.AF |
---|