• Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems.
• Provide multizone control by using a separate circulator and R845 Relay for each zone.
• Include diaphragm powerhead and Micro Switch™ assembly that respond to temperature changes in boiler water.
• Mount directly to boiler.
• Select models include large transformers and extra terminals for supplying power to low voltage zone valves.
• Require 24 Vac thermostat with heat anticipator set at 0.2 A (plus current draw of gas valve on L8124E).
• TRADELINE models include tube of heat conductive compound and range stops.Triple Aquastat Relay for High Limit Protection, Low Limit and Circulation ControlOperating Range, Low Limit (F) | 110 F to 220 F adj. |
---|
Overview | Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems, including domestic hot water service. |
---|
Operating Range, Low Limit (C) | 43 C to 104 C adj. |
---|
Operating Range, High Limit (F) | 130 F to 240 F adj. |
---|
Maximum Safe Operating Pressure (psi) | 200 psi on outside of immersion well, 100 psi on capsule if inserted directly. |
---|
Operating Range, High Limit (C) | 54 C to 116 C adj. |
---|
Maximum Safe Operating Pressure (kPa) | 1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly. |
---|
Application | High Limit Protection, Low Limit and Circulation Control |
---|
Electrical Ratings (burner AFL) | 3.7 A @ 240 Vac |
---|
Electrical Ratings (burner ALR) | 44.4 A @ 120 Vac |
---|
Electrical Ratings (circulator AFL) | 3.7 A @ 240 Vac |
---|
Electrical Ratings (circulator ALR) | 22.2 A @ 240 Vac |
---|
Operating Temperature Range (F) | High Limit-- 130 F to 240 F adjustable; Low Limit-- 110 F to 220 F adjustable |
---|
Operating Temperature Range (C) | High Limit-- 54 C to 116 C adjustable; Low Limit-- 43 C to 104 C adjustable |
---|
Dimensions (in.) | 6 1/8 in. high x 4 3/8 in. wide x 3 1/16 in. deep |
---|
Dimensions (mm) | 156 mm high x 111 mm wide x 78 mm deep |
---|
Insulation Depth (in.) | 3 in. |
---|
Insulation Depth (mm) | 76 mm |
---|
Operating Humidity Range (% RH) | 0 to 95% RH, non-condensing |
---|
Differential Temperature (F) | High limit : 10 F fixed; low limit: 10-25 F adj. |
---|
Maximum Ambient Temperature (F) | 150 F at switches; 265 F at sensing element |
---|
Maximum Ambient Temperature (C) | 66 C at switches, 129 C at sensing element. |
---|
Approvals, Underwriters Laboratories Inc | UL Listed (models with well): File No. MP466, Guide No. MBPR; UL Component Recognized (models without well): File No. MP466, Guide No. MBPR2 |
---|
Approvals, Canadian Standards Association | Certified: File No. LR1620, Guide No. 400-E-O |
---|
Includes | 3 in. insertion well and ground screw. |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|