• Three-diaphragm design minimizes calibration shift with static pressure changes in velocity pressure applications.
• Not sensitive to normal supply air variations.
• Continuous static, total, velocity, or differential pressure indication available by using differential pressure gage.Static Pressure Sensor, Direct or Reverse ActingApplication Type | Static Pressure |
---|
Overview | One-pipe, direct-or reverse-acting pressure sensor used with RP908/RP920 Controllers to provide control of duct static, velocity, or differential pressure in airflow applications. Replacement devices available for Johnson, Powers, Robertshaw, Barber-Colma |
---|
Setpoint Range (in. wc) | 0 in. wc. to 7 in. wc. (Adjustable) |
---|
Setpoint Range (kPa) | 0 kPa to 1.7 kPa (Adjustable) |
---|
Connections | Push-on barb for 1/4 in (6 mm) Diameter tubing |
---|
Action | Can be set for Direct Acting or Reverse Acting |
---|
Mainline Air Pressure (max.) (psi) | 25 psi |
---|
Output Pressure Range (psi) | 3 psi to 15 psi |
---|
Pressure Range (psi) | 2 in. wc |
---|
Output Pressure Range (kPa) | 21 kPa to 103 kPa |
---|
Mainline Air Pressure (max.) (kPa) | 175 kPa |
---|
Pressure Range (kPa) | 0.5 kPa |
---|
Mainline Air Pressure (min.) (kPa) | 112 kPa |
---|
Span (Non-Adjustable) (in. wc) | 2 in. wc. |
---|
Span (Non-Adjustable) (kPa) | 0.5 kPa |
---|
Mainline Air Pressure (min) (psi) | 16 psi |
---|
Maximum Safe Static Pressure (in. wc) | 28 in. wc |
---|
Maximum Safe Static Pressure (kPa) | 7 kPa |
---|
Maximum Safe Operating Pressure (psi) | 25 psi |
---|
Airflow Usage | 0.021 cfm (9.9 ml/s) |
---|
Maximum Safe Operating Pressure (kPa) | 172 kPa |
---|
Comments | The setpoint determines the midpoint of the span. |
---|
Temperature Range (F) | 40 F to 120 F |
---|
Temperature Range (C) | 4 C to 50 C |
---|
Dimensions (in.) | 8 in high, 9 in wide, 4 1/8 in deep |
---|
Dimensions (mm) | 203 mm high, 228 mm wide, 105 mm deep |
---|
Product Family
Cross Reference
Honeywell, Inc. | PP905B1008 |
| |
Siemens Building Technologies | 141-0593 |
Comment | Low Diff. Pressure Transmitter |
|
Manufacturer Suggested Replacements |
Honeywell, Inc. | PP905B1008 |
| |
Siemens Building Technologies | 141-0593 |
Comment | Low Diff. Pressure Transmitter |
|
Manufacturer Suggested Replacements |
|
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!
Add Review
|