• Uses standard Echelon® LonMark Unit Ventilator functional profile for openness and interoperability with Lon Mark devices.
• Applications include unit ventilators with up to two stages heat/cool; floating heat/cool/economizer, pulse width modulating (PWM) heat/cool/economizer; ASHRAE Cycles I, II, III.
• Two unused digital outputs can be used as free points controlled by the network for lighting, exhaust fan.
• Can be used for indoor air quality control using an external sensor/control and economizer minimum position reset.
• Provides optional energy-saving setpoints for heating/cooling in unoccupied/occupied and standby modes.
• Optional control sequence shutdown via window/door open digital input.
• On-board network jacks for quick commissioning and troubleshooting using the E-Vision configuration tool.
• On-board status LED.
• Free topology transceiver (FTT) for flexible installation.
• UL94-5V flame-retardant construction.Fan Coil Unit Controller, 2 Heat / 2 Cool, Small Sytems (<20 I/O Points)Application Size | 2 Heat / 2 Cool |
---|
I/O Count | 8 Digital Outputs (triac), 2 Analog Inputs (resistive), 2 Analog Inputs (voltage), 4 Digital Inputs |
---|
Overview | W7753A is a direct digital controller for unit ventilators with staged, floating, or pulse width modulation output using pre programmed heating, cooling, economizer, and ASHRAE cycles I, II, or III algorithms. |
---|
Setpoint Temperature Range (F) | 55 F to 85 F |
---|
Setpoint Temperature Range (C) | 13 C to 29 C |
---|
Used With | See Application Selection Guide (63-7044) |
---|
Application | Unit Ventilator |
---|
Network Communications | LonWorks Bus |
---|
Commissioning Software | LNS Plug-in |
---|
Output Type | Staged On/Off, Floating, Pulse Width Modulation |
---|
Dimensions (in.) | 5 5/8 in. high x 6 in. wide x 2 1/8 in. deep |
---|
Dimensions (mm) | 143 mm high x 152 mm wide x 54 mm deep |
---|
Shipping Temperature Range (F) | -40 F to +150 F |
---|
Shipping Temperature Range (C) | -40 C to +65 C |
---|
Approvals, Underwriters Laboratories Inc | UL 916 |
---|
Approvals, Federal Communications Commission | FCC part 15 Class B requirements |
---|
Comments | One T7770 wall module input |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page