• Corrosion resistant materials.
• Simple plug-in air head connections.
• Factory calibrated.
• Continuous relative humidity indication available by using receiver gage.
• Integral or external restriction can be used.Pneumatic Humidity Sensor, 1 or 2 pipes, 15 to 85% RHApplication Type | Humidity Sensor |
---|
Humidity Sensor Range | 15 to 85% RH |
---|
Overview | One- or two-pipe, direct-acting humidity sensor used with RP908/RP920 Controllers to provide proportional control of pneumatic valve or damper actuators in systems requiring humidification or dehumidification control. |
---|
Connections | Push-on barb for 5/32 in. (4 mm) O.D. tubing |
---|
Output Pressure Range (psi) | 3 psi to 15 psi |
---|
Output Pressure Range (kPa) | 21 kPa to 103 kPa |
---|
Supply Pressure (psi) | 16-21 psi |
---|
Supply Pressure (kPa) | 110-145 kPa |
---|
Maximum Operating Temperature (F) | 125 F |
---|
Maximum Operating Temperature (C) | 52 C |
---|
Maximum Safe Operating Pressure (psi) | 25 psi |
---|
Airflow Usage | 0.022 scfm (10.4 mL/s) |
---|
Maximum Safe Operating Pressure (kPa) | 172 kPa |
---|
Comments | Order Cover Separately |
---|
Mounting | Vertical or Horizontal Wall Mounting or Mounted in Duct Sampling Chamber |
---|
Dimensions (in.) | 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep |
---|
Dimensions (mm) | 88 mm high x 51 mm wide x 41 mm deep |
---|
Product Family
All orders are shipped same-day if the order is received by 1:00 PM Central Time. We ship worldwide.
UPS Hoilday Delivery Schedule
For more infomation about Returns visit Returns
For more informatrion about Warranty visit Warranty page.
You can also find answers to some common questions on our FAQ page
Reviews
Not reviewed yet, be the first to write one!